headerphoto

 

Product Selection

 

Note:  for all systems, if make-up can be shut off between BHR and outlet (user), a pressure relief valve should be installed for 1.5x inlet pressure, or 150 psig Max.

 

tank

BHR-15   

Non-registered plant applications
Steam boilers operating at less than 15 psig
Does not require TSSA certification
Any boiler size.

 

Design Information:   

50 IG storage capacity at overflow
1 ¼-inch make-up inlet/outlet connections
2-inch Flash Steam outlet
100 linear feet, 3/8-inch SS coils in 10 foot sections
1.5 million BTU heat transfer at 150 psig MAWP
40 - 60 IGPM make-up rate at 60 - 70 psig

Heat Exchanger: BHR-HX-10

 

 

tank

BHR-16LP  

Non-registered plant or, with registered pressure vessel flash chamber, plants operating above 15 psig.

 

Design Information:   

18 IG storage capacity at overflow
2-inch flash steam outlet
30 linear feet, 3/8-inch stainless steel coils in 10 foot sections
10 – 20 IGPM make-up rate at 60 – 70 psig

Heat Exchanger: BHR-HX-3

 

spec sheet: click here (pdf)

 

tank

BHR-24HM   

Registered plant installations
Firetube boilers up to 150 BHP
Coil Tube or Low Water Mass boilers up to 300 BHP

 

Design Information:   

50 IG storage capacity at overflow
10 5/8" diameter Flash Chamber rated for 100 psig MAWP
3" atmospheric relief on storage tank
1 ¼-inch make-up inlet/outlet connections
2-inch Flash Steam outlet
100 linear feet, 3/8-inch SS coils in 10 foot sections
1.5 million BTU heat transfer at 150 psig MAWP
40 - 60 IGPM make-up rate at 60 - 70 psig

Heat Exchanger: BHR-HX-10

 

spec sheet: click here (pdf)

 

tank

BHR-36HM   

Registered plant installations
TSSA certified and CRN registered
Firetube or High Mass boilers up to 600 BHP
Coil Tube or Low Mass boilers up to 800 BHP

 

Design Information:   

MAWP: 100 psig
24 Ft3 (150 IG) capacity
36” diameter x 75.5” total height
150 linear feet, 3/8-inch SS coils in 10 foot sections
2.4 million BTU heat transfer at 150 psig MAWP
60 - 80 IGPM make-up rate at 60 - 70 psig
2" Cooling Inlet/Outlets
4" atmospheric relief on storage tank

Heat Exchanger: BHR-HX-15

 

spec sheet: click here (pdf)

 

tank

BHR-48HM   

Registered plant installations
TSSA certified and CRN registered
High Mass boilers up to 100,000#/Hr steam flow

 

Design Information:   

MAWP: 100 psig
64 Ft3 (400 IG) capacity
48” diamter x 99” total height
150 linear feet, 3/8-inch SS coils in 10 foot sections
2.4 million BTU heat transfer at 150 psig MAWP
60 - 80 IGPM make-up rate at 60 - 70 psig
2" Cooling Inlet/Outlets
4" atmospheric relief on storage tank

Heat Exchanger: BHR-HX-15

 

spec sheet: click here (pdf)

 

Heat Exchangers

 

BHR-HX-10 Heat Exchanger

BHR-HX-10   

1 ¼ inch 316 stainless steel nipples and union

2 x 2 inch schedule 40 square tube manifold complete with 10 Swagelok 316 stainless steel compression connectors

10 x 3/8 inch 304 stainless steel tubes in 10 foot lengths

MAWP: 300 psig

 

BHR-HX-10 for BHR-15 & BHR-24HM

 

Heat Exchanger

 

BHR-HX-15   

2 inch 316 stainless steel nipples and union

2 x 2 1/2 inch schedule 40 square tube manifold complete with 15 Swagelok 316 stainless steel compression connectors

15 x 3/8 inch 304 stainless steel tubes in 10 foot lengths

MAWP: 300 psig

BHR-HX-15 in BHR-48HM

 

 

 

 

 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Click to get the latest version >> In order to view & print these files, you must have Adobe Acrobat Reader installed on your computer (It's FREE). If you already have it installed, just click on the link & Acrobat will open & download the information in your browser window.